Toyota Venza manuals

Toyota Venza: Inspection

INSPECTION

PROCEDURE

1. INSPECT SHIFT SOLENOID VALVE SL

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Shift Solenoid Valve SL

Standard Resistance:

Tester Connection

Condition

Specified Condition

Solenoid Connector (SL) - Solenoid Body (SL)

20°C (68°F)

11 to 15 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead to the terminal of the solenoid connector, and a negative (-) battery lead to the solenoid body, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

2. INSPECT SHIFT SOLENOID VALVE SLT

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

3. INSPECT SHIFT SOLENOID VALVE SLU

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SLU)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

4. INSPECT SHIFT SOLENOID VALVE SL1

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL1)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

5. INSPECT SHIFT SOLENOID VALVE SL2

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL2)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

6. INSPECT SHIFT SOLENOID VALVE SL3

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL3)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

7. INSPECT SHIFT SOLENOID VALVE SL4

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL4)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

Removal
REMOVAL PROCEDURE 1. REMOVE AUTOMATIC TRANSAXLE ASSEMBLY HINT: See the steps from "Remove Engine Assembly with transaxle" through "Remove Automatic Transaxle Assembly" (See p ...

Reassembly
REASSEMBLY PROCEDURE 1. INSTALL SHIFT SOLENOID VALVE SL4 (a) Coat the shift solenoid valve SL4 and bolt with ATF. Text in Illustration *1 Lock Pla ...

Other materials about Toyota Venza:

Electronic Circuit Inspection Procedure
ELECTRONIC CIRCUIT INSPECTION PROCEDURE 1. BASIC INSPECTION (a) WHEN MEASURING RESISTANCE OF ELECTRONIC PARTS (1) Unless otherwise stated, all resistance measurements are standard values measured at an ambient temperature of 20°C (68°F). Resistance meas ...

If you have a flat tire
Remove the flat tire and replace it with the spare provided. - Before jacking up the vehicle • Stop the vehicle on a hard, flat surface. • Set the parking brake. • Shift the shift lever to “P”. • Stop the engine. • Turn on the emergency f ...

Relay
On-vehicle Inspection ON-VEHICLE INSPECTION PROCEDURE 1. INSPECT DOME CUT RELAY (a) Measure the resistance according to the value(s) in the table below. Standard Resistance: Tester Connection Condition ...

© 2016-2025 Copyright www.tovenza.com

0.1147