Toyota Venza manuals

Toyota Venza: Inspection

INSPECTION

PROCEDURE

1. INSPECT SHIFT SOLENOID VALVE SL

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Shift Solenoid Valve SL

Standard Resistance:

Tester Connection

Condition

Specified Condition

Solenoid Connector (SL) - Solenoid Body (SL)

20°C (68°F)

11 to 15 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead to the terminal of the solenoid connector, and a negative (-) battery lead to the solenoid body, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

2. INSPECT SHIFT SOLENOID VALVE SLT

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

3. INSPECT SHIFT SOLENOID VALVE SLU

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SLU)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

4. INSPECT SHIFT SOLENOID VALVE SL1

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL1)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

5. INSPECT SHIFT SOLENOID VALVE SL2

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL2)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

6. INSPECT SHIFT SOLENOID VALVE SL3

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL3)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

7. INSPECT SHIFT SOLENOID VALVE SL4

(a) Measure the resistance according to the value(s) in the table below.

Text in Illustration

*1

Component without harness connected:

(Shift Solenoid Valve SL4)

Standard Resistance:

Tester Connection

Condition

Specified Condition

1 - 2

20°C (68°F)

5.0 to 5.6 Ω

If the value is not as specified, replace the shift solenoid valve.


(b) Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

NOTICE:

When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

OK:

The valve moves and makes an operating sound.

If the operation cannot be done as specified, replace the shift solenoid valve.

Disassembly
DISASSEMBLY PROCEDURE 1. REMOVE TRANSMISSION WIRE 2. REMOVE ATF TEMPERATURE SENSOR ASSEMBLY (a) Remove the 4 bolts, ATF temperature sensor assembly and clamp from the valve body ...

Reassembly
REASSEMBLY PROCEDURE 1. INSTALL SHIFT SOLENOID VALVE SL4 (a) Coat the shift solenoid valve SL4 and bolt with ATF. Text in Illustration *1 Lock Pla ...

Other materials about Toyota Venza:

Removal
REMOVAL CAUTION / NOTICE / HINT HINT: Use the same procedure for the RH side and LH side. The procedure listed below is for the LH side. PROCEDURE 1. DISCONNECT CABLE FROM NEGATIVE BATTERY TERMINAL CAUTION: Wait at least 90 seconds aft ...

Sound Signal Circuit between Navigation Receiver Assembly and Stereo Jack Adapter
DESCRIPTION The No. 1 stereo jack adapter assembly sends the sound signal from an external device to the navigation receiver assembly via this circuit. The sound signal that has been sent is amplified by the navigation receiver assembly and then is sent ...

Inspection
INSPECTION PROCEDURE 1. INSPECT PAD LINING THICKNESS (a) Using a ruler, measure the pad lining thickness. Text in Illustration *1 Ruler Standard thickness of a new pad: 10.0 mm (0.394 ...

© 2016-2026 Copyright www.tovenza.com

0.1297